2015 IECC with Amendments (Pennsylvania)

Commercial Energy Efficiency Code Application to replacement fenestration products Where some or all of an existing fenestration unit is replaced with a new fenestration product, including slash and glazing, the replacement fenestration unit shall meet the applicable…

Last changed 8 years ago.

Extracted view for reading · Original for compliance evidence

Lifecycle

  1. Effective
  2. Last change

Country / jurisdiction: United States · Year: 2018 · Status: In force · Level: State/Provincial · Type: Voluntary

Commercial Energy Efficiency Code

Application to replacement fenestration products

Where some or all of an existing fenestration unit is replaced with a new fenestration product, including slash and glazing, the replacement fenestration unit shall meet the applicable requirements for U-factor and SHGC in Table C402.4.

Building Envelope Requirements

Building thermal envelope assemblies for building that are intended to comply with the code on a perspective basis, in accordance with the compliance path described in Item 2 of Section C401.2, shall comply with the following:

The opaque portion of the building thermal envelope shall comply with the specific insulation requirements of Section C402.2 and the thermal requirements of either the R-value –based method of section C 402.1.3; the U-, C-, F-Factor-based method of Section C402.1.4; or the component performance alternative of Section C402.1.5

Roof solar reflectance and thermal emittance shall comply with Section C402.3

Fenestration in building envelope assemblies shall comply with Section C402.4

Air leakage of building envelope assemblies shall comply with Section C402.5

Prescriptive Compliance

Fenestration shall comply with Sections C402.4 through C402.4.4 and Table C402.4. Daylight responsive controls shall comply with this section and Section C405.2.3.1.

Vertical Fenestration: New vertical fenestration area that results in a total building fenestration area less than or equal to that specified in Section C402.4.1 shall comply with Section C402.4. Additions with vertical fenestration that result in a total building fenestration area greater than Section C402.4.1 or additions that exceed the fenestration area greater than Section C402.4.1 shall comply with Section C402.4.1.1 for the addition only. Additions that result in a total building vertical glass area exceeding that specified in Section C402.4.1.1 shall comply with Section C407.

Skylight area

The skylight area shall not be greater than 3 percent of the gross roof area.

In an enclosed space greater than 2,500 square feet (232 m2) in floor area, directly under a roof with not less than 75 percent of the ceiling area with a ceiling height greater than 15 feet (4572 mm), and used as an office, lobby, atrium, concourse, corridor, storage space, gymnasium/exercise center, convention center, automotive service area, space where manufacturing occurs, non-refrigerated warehouse, retail store, distribution/sorting area, transportation depot or workshop, the total daylight zone under skylights shall be not less than half the floor area and shall provide one of the following:

A minimum skylight area to daylight zone under skylights of not less than 3 percent where all skylights have a VT of at least 0.40 as determined in accordance with Section C303.1.3.

A minimum skylight effective aperture of at least 1 percent, determined in accordance with Equation 4-4.

Skylight Effective Aperture= 0.85. ????????????h?? ???????? . ????????????h?? ???? . ????/ ????????????h?? ???????? ?????????? ????????????h?? (Equation 4-4)

where:

Skylight area = Total fenestration area of skylights.

Skylight VT = Area weighted average visible transmittance of skylights.

WF = Area weighted average well factor, where well factor is 0.9 if light well depth is less than 2 feet (610 mm), or 0.7 if light well depth is 2 feet (610 mm) or greater.

Light well depth = Measure vertically from the underside of the lowest point of the skylight glazing to the ceiling plane under the skylight.

Air leakage

The thermal envelop of buildings shall comply with Sections C402.5.1 through C402.5.8, or the building thermal envelope shall be tested in accordance with ASTM E 779 at a pressure differential of 0.3 inch water gauge (75Pa) or an equivalent method approved by the code official and deemed to comply with the provisions of this section when the tested air leakage rate of the building thermal envelope is not greater than 0.4 cfm/ft2 (0.2 L/s.m2

Official source: https://codes.iccsafe.org/content/IECC2015

Source

https://www.iea.org/policies/7125

Canonical document at the regulator. Always cite this URL — not the Vantage detail page — in compliance evidence.

Related in International

INTEnergy Newsoilprice:oilprice-article-45339NewsIn force

Egypt’s LNG Comeback Is Set to Start in Cyprus

Egypt’s gas sector is running short of domestic gas just as Cyprus prepares to become a producer. The recently approved Cronos project offshore Cyprus (expected to deliver up to 2.8 million tonnes per year of LNG from 2028) offers a three-way bargain. Cyprus gains an export route it cannot economically build alone; Egypt secures feedstock for infrastructure increasingly constrained by falling domestic production, and Europe gains another non-Russian source. The logic is compelling, but technical, commercial and geopolitical risks could still…

23 hours ago
INTEnergy Newsoilprice:oilprice-article-45338NewsIn force

East Africa’s Oil Rivalry Spurs Multi-Billion-Dollar Projects Across The Region

Last month, we reported that Nigerian billionaire and Africa’s richest man, Aliko Dangote, has agreed to build a $17 billion (Ksh2.2 trillion), 700,000-barrel-per-day refinery on Kenya’s Lamu Island that would process crude not only for Kenya but also its neighbors such as Uganda, Rwanda, Burundi, South Sudan and the DRC. The giant refinery--Africa’s second largest refinery behind only Nigeria’s Dangote refinery--would easily exceed East Africa’s current refined fuel demand of roughly 450,000 bpd, leaving room to supply…

24 hours ago
INTEnergy Newsoilprice:oilprice-article-45337NewsIn force

DoE Begins Tests for Fracked Geothermal

The Trump administration is no friend of wind and solar. Axed subsidies and project suspensions have been the attitude towards those alternative forms of energy. Geothermal, however, is something else. The current Department of Energy is very much for it. In fact, it is so much for it that it funded an experiment that would show whether fracking technology could be used to generate geothermal anywhere in the world. Geothermal energy is, simply put, heat. It is heat that is generated from the decay of radioactive elements in the planet’s mantle.…

1 day ago
INTEnergy Newsoilprice:oilprice-article-45336NewsIn force

Europe Heads Into Winter With Gas Storage at a Two-Decade Low

Europe is heading for the winter with one of the lowest levels of gas in storage in the past two decades as the war in the Middle East crippled LNG supply from Qatar, sent gas and LNG prices in Europe and Asia skyrocketing, and intensified competition for the shrunk pool of readily available global LNG cargoes. A perfect storm of elevated demand for filling depleted storage and electricity during the summer heatwaves, and slashed global LNG supply with Qatar’s cargoes trapped behind the Strait of Hormuz have pushed European benchmark prices…

1 day ago
INTEnergy Newsrigzone:https://www.rigzone.com/news/wire/oil_rises_as_iran_deal_hopes_fade-27-aug-2026-184478-article/?rss=trueNewsIn force

Oil Rises as Iran Deal Hopes Fade

Oil rose as doubts grew over a broader US-Iran agreement.

1 day ago